Model for choosing optimal water flow rate for tank wall cooling

 

Basmanov Oleksii

National University of Civil Defence of Ukraine

https://orcid.org/0000-0002-6434-6575

 

Maksymenko Maksym

National University of Civil Defence of Ukraine

http://orcid.org/0000-0002-1888-4815

 

DOI: https://doi.org/10.52363/2524-0226-2023-38-1

 

Keywords: tank fire, thermal influence of fire, heat transfer, water cooling, water flow rate

 

Аnnotation

 

In this paper, we have considered the problem of choosing the optimal water flow rate for cooling the tank wall with water in the event of a fire in the adjacent tank. The optimal water flow rate is understood as the minimal flow ensuring a sufficient level of cooling. The choice of the water flow rate is based on the solution of the thermal balance equation for the tank wall and the thermal balance equation for the water film. The model takes into account the radiant heat transfer between the flame, the tank wall, the environment and the internal space of the tank. The convective heat transfer from the tank wall to water and vapor-air mixture is also taken into account. Here, we have developed an algorithm for determining the optimal water flow for cooling the tank wall. Solving the problem of choosing the rate of the cooling water flow is reduced to the sequential solution of the problems to determine the temperature distribution along the tank wall and the water film. We have constructed the functional dependence of optimal water flow rate for tank cooling on the direction and velocity of the wind. The inclination of the flame by the wind towards the adjacent tank increases the relevant heat influx, which requires a greater intensity of cooling. On the contrary, when the direction of the wind is away from the adjacent tank, the heat flux decreases. At the same time, for wind velocity greater than a certain value, the heat flux decreases to such an extent that there is no more need to cool the walls of the adjacent tank. With the perpendicular direction of the wind, at certain velocity values, there is no need to cool the walls of the adjacent tank either. The obtained results can be used to determine the rate of water flow for cooling the tank wall in the event of a fire in an adjacent tank.

 

References

 

  1. Yang,, Khan, F., Neto, E. T., Rusli, R., Ji, J. (2020) Could pool fire alone cause a domino effect? Reliability Engineering & System Safety, 202, 106976. doi: 10.1016/j.ress.2020.106976
  2. Reniers, G., Cozzani, V. (2013). Features of Escalation Scenarios. Domino Effects in the Process Industries. Elsevier, 30–42. doi: 1016/B978-0-444-54323-3.00003-8
  3. Huang, K., Chen, G., Khan, F., Yang, Y. (2021). Dynamic analysis for fire-induced domino effects in chemical process industries. Process Safety and Environmental Protection, 148, 686–697. doi: 1016/j.psep.2021.01.042
  4. Hemmatian, B., Abdolhamidzadeh, B., Darbra, R., Casal, J. (2014). The significance of domino effect in chemical accidents. Journal of Loss Prevention in the Process Industries, 29, 30–38. doi: 10.1016/j.jlp.2014.01.003
  5. Wu, B., Roy, S. P., Zhao, X. (2020). Detailed modeling of a small-scale turbulent pool fire. Combustion and Flame, 214, 224–237. doi: 10.1016/j.combustflame.2019.12.034
  6. Shi, C., Liu, W., Hong, W., Zhong, M., Zhang, X. (2019). A modified thermal radiation model with multiple factors for investigating temperature rise around pool fire. Journal of Hazardous Materials, 379, 120801. doi: 10.1016/j.jhazmat.2019.120801
  7. Ahmadi, O., Mortazavi, S. B., Pasdarshahri, H., Mohabadi, H. A. (2019). Consequence analysis of large-scale pool fire in oil storage terminal based on computational fluid dynamic (CFD). Process Safety and Environmental Protection, 123,379–389. doi: 10.1016/j.psep.2019.01.006
  8. Li, Y., Jiang, J., Zhang, Q., Yu, Y., Wang, Z., Liu, H., Shu, C.-M. (2019). Static and dynamic flame model effects on thermal buckling: Fixed-roof tanks adjacent to an ethanol pool-fire. Process Safety and Environmental Protection, 127,23–35. doi: 10.1016/j.psep.2019.05.001
  9. Yi, H., Feng, Y., Wang, Q. (2019). Computational fluid dynamics (CFD) study of heat radiation from large liquefied petroleum gas (LPG) pool fires. Journal of Loss Prevention in the Process Industries, 61, 262–274. doi: 10.1016/j.jlp.2019.06.015
  10. Elhelw, M., El-Shobaky, A., Attia, A., El-Maghlany, W. M. (2021). Advanced dynamic modeling study of fire and smoke of crude oil storage tanks. Process Safety and Environmental Protection, 46, 670–685. doi: 10.1016/j.psep.2020.12.002
  11. Wang, J., Wang, M., Yu, X., Zong R., Lu, S. (2022). Experimental and numerical study of the fire behavior of a tank with oil leaking and burning. Process Safety and Environmental Protection, 159, 1203–1214. doi: 10.1016/j.psep.2022.01.047
  12. Semerak,, Pozdeev, S., Yakovchuk, R., Nekora, O., Sviatkevich, O. (2018). Mathematical modeling of thermal fire effect on tanks with oil products. MATEC Web of Conferences, 247(00040). doi: 10.1051/matecconf/201824700040
  13. Abramov, Y. A., Basmanov, O. E., Mikhayluk, A. A., Salamov, J. (2018). Model of thermal effect of fire within a dike on the oil tank. Naukovyi Visnyk NHU, 2, 95–100. doi: 10.29202/nvngu/2018-2/12
  14. Basmanov, O., Maksymenko, M. (2022). Modeling the thermal effect of fire to the adjacent tank in the presence of wind. Problems of emergency situations, 1(35), 239–253. doi: 10.52363/2524-0226-2022-35-18
  15. Wu, Z., Hou, L., Wu, S., Wu, X., Liu, F. (2020). The time-to-failure assessment of large crude oil storage tank exposed to pool fire. Fire Safety Journal, 117 (103192). doi: 10.1016/j.firesaf.2020.103192.
  16. Espinosa, N., Jaca, R. C., Godoy, L. A. (2019). Thermal effects of fire on a nearby fuel storage tank. Journal of Loss Prevention in the Process Industries,62(103990). doi:10.1016/j.jlp.2019.103990
  17. Maksymenko, M. (2023). A model of cooling the tank shell by water in the case of a fire in an adjacent tank. Problems of emergency situations, 1 (37), 156– doi: 10.52363/2524-0226-2023-37-11
  18. Abramov, Y., Basmanov, O., Salamov, J., Mikhayluk, A., Yashchenko, O. (2019). Developing a model of tank cooling by water jets from hydraulic monitors under conditions of fire. Eastern-European Journal of Enterprise Technologies, Ecology, 1/10 (97), 14–20. doi: 15587/1729-4061.2019.154669
  19. Fire Fighting Leader Handbook. (2017). Kyiv book and magazine factory, 2017, 320
  20. Zhang, X., Hu, L., Wu, L., Kostiuk, L. W. (2019). Flame radiation emission from pool fires under the influence of cross airflow and ambient pressure. Combustion and Flame, 202, 243–251. doi: 10.1016/j.combustflame.2019.01.015