DOI: https://doi.org/10.52363/2524-0226-2024-39-18
Keywords: explosion and fire hazard, overpressure of explosion, flammable dust, explosion dust, category of premises according to fire and explosion hazard
Аnnotation
Estimated explosion pressure of the dust-air mixture in the industrial premises was evaluated taking into account air humidity to determine the category of the premises according to explosion and fire hazard. The study presents data that demonstrate the presence of water vapor in the air and reflect its sensitivity to ambient temperature. During the research, the calculation of the overpressure of the explosion in the working room and equipment with a dust-air mixture was carried out. At the same time, a hypothesis was put forward regarding the influence of humidity in the room with dust-air mixtures on the obtained value of the calculated overpressure of the explosion. The error with which this value will be determined, in turn, can lead to the adoption of a wrong decision regarding the specified category of the premises in terms of explosion and fire hazard. In order to test the proposed hypothesis, calculations were carried out for two cases – without taking into account and taking into account the humidity in the air of the surrounding environment. The input values for the calculations were chosen in accordance with the requirements for ensuring environmental parameters in industrial premises with dust-air mixtures. The results obtained during the research confirmed the proposed hypothesis regarding the influ-ence of humidity on the value of the calculated overpressure of the explosion. The influence of humidity in the environment on the accuracy of the obtained value of the calculated excess pressure is a recognized fact and requires additional research. The results of the estimates obtained during the study confirm the need to take into account the influence of the humidity of the environment in the production room on the calculated value of the excess pressure of the explosion. Based on the results of these calculations, a conclusion is made regarding the belonging of a room with a dust-air mixture to a certain category in terms of explosion-fire hazard, as well as the need to take precautionary measures to reduce the fire-explosion hazard of environments in industrial premises.
References
- DSTU B V.1.1–36:2016. Vyznachennia katehorii prymishchen, budynkiv ta zovnishnikh ustanovok za vybukhopozhezhnoiu ta pozhezhnoiu nebezpekoiu, 31. Available at: https://zakon.rada.gov.ua/rada/show/v0158858–16#Text
- The Confederation of Fire Protection Associations Europe (CFPA–Europe). (2022). Available at: https://cfpa–e.eu/
- National Fire Protection Association (NFPA). (2022). Available at: https://www.nfpa.org
- British Standards Institution (BSI). (2022). Available at: https://www.bsigroup.com/
- NFPA 68. (2002). Guide for Venting of Deflagrations. Available at: https://www.nfpa.org/codes–and–standards/all–codes–and–standards/list–of–codes–and–standards/detail?code=68
- Policy on Fire Protection Rules Available at: https://www.euspa.europa.eu/
sites/default/files/policy_on_fire_protection_rules.pdf - Darie, M., Burian, S., Ionescu, J., Csaszar, T., Moldovan, L., Colda, C., Andriş, A. (2014). Air humidity – a significant factor on ignition sensitivity of gaseous explosive atmospheres. Proc. The Xth Environmental legislation, safety engineering and disaster management, Cluj–Napoca, Romania. 47. Available at: https://www.researchgate.
net/publication/272158810_AIR_HUMIDITY_–_A_SIGNIFICANT_FACTOR_ON_
IGNITION_SENSITIVITY_OF_GASEOUS_EXPLOSIVE_ATMOSPHERES - Darie, M., Burian, S., Csaszar, T., Moldovan, L., Moldovan, C. (2017). New aspects regarding ignition sensitivity of air–methane mixtures Environmental Engineering and Management Journal, Romania. June 2017, 16, 6, 1263–1267. Available at: https://www.researchgate.net/profile/Doru–Cioclea/publication/319523058_Method_
for_improving_the_management_of_mine_ventilation_networks_after_an_explosion/links/5b17c994aca272021ce9153b/Method–for–improving–the–management–of–mine–ventilation–networks–after–an–explosion.pdf#page=25 - Khudhur, D. A., Ali, M. W., Abdullah, T. A. T. (2020). Mechanisms, Severity and Ignitability Factors, Explosibility Testing Method, Explosion Severity Characteristics, and Damage Control for Dust Explosion: A Concise Review. Journal of Physics: Conference Series. «International laser technology and optics symposium in conjunction with photonics meeting 2020» (ILATOSPM), 22–23 October 2020, Malaysia, Johor. doi:10.1088/1742–6596/1892/1/012023.
- Kostenko, V., Liashok, Y., Zavialova, O., Pozdieiev, S., Kostenko, T. (2020). The deformation dynamics of the experimental adit’s material during a coal dust explosion. Eastern-European Journal of Enterprise Technologies, 4, 7–106, 54–62. doi: 10.15587/1729-4061.2020.209409
- Roianov, O., Katunin, A., Melezhyk, R., Bogatov, O. (2022). Evaluation of the influence of air humidity on the calculated explosion overpressure. Problems of Emergency Situations, 2(36), 312–324. Available at: http://repositsc.nuczu.edu.ua/handle/
123456789/17442 - Shun‑Chieh Chang, Yu‑Chi Cheng, Xin‑Hai Zhang, Chi‑Min Shu. (2021). Efects of moisture content on explosion characteristics of incense dust in incense factory. Journal of Thermal Analysis and Calorimetry. Available at: https://d-nb.info/123260920X/34