Experimental determination of the inertia of activation of sprinklers of automatic water extinguishing systems

 

Serhij Bondarenko

National University of Civil Defence of Ukraine

http://orcid.org/0000-0002-4687-1763

 

Michailo Murin

National University of Civil Defence of Ukraine

http://orcid.org/0000-0002-9898-0128

 

Igor Jakovlev

National University of Civil Defence of Ukraine

http://orcid.org/0000-0003-2802-3733

 

DOI: https://doi.org/10.52363/2524-0226-2021-33-11

 

Keywords: automatic water fire extinguishing system, sprinkler, response time index, linear speed of fire development, calculated area for water consumption

 

Abstract

Experimental data on the inertia of sprinklers with a response temperature of 57 ºС were obtained, taking into account the rate of temperature rise, and an empirical dependence of the response time of a sprinkler from the moment of fire occurrence was obtained. This makes it possible to evaluate the use of this type of sprinklers for the protection of various premises, depending on the class of fire hazard. When choosing the initial data for the design of automatic sprinkler systems for water fire extinguishing, depending on the class of premises for fire hazard, two approaches are visible. For rooms of class OH, with an increase in fire hazard, the intensity of the extinguishing agent supply remains constant (I0 = 5 mm/min), and the extinguishing area for calculating the water consumption increases (Fр = 72 m2 for OH1, Fр = 144 m2 for OH2, Fр = 216 m2 for OH3, Fp = 360 m2 for OH4). For HHP premises, a different approach is taken. When designing a sprinkler automatic water fire extinguishing system, the calculated area for determining the total water consumption remains constant (Fр = 260 m2) and the intensity of the extinguishing agent supply changes (I0 = 7.5 mm/min for ННР1, I0 = 10 mm/min for ННР2, I0 = 12.5 mm/min for HHP3). However, both the first approach and the second imply that the area of fire extinguishing remains a fixed value, and the linear rate of fire development is not explicitly taken into account anywhere. Therefore, obtaining data on the response time of the sprinkler, depending on the rate of rise of the fire temperature in the protected room, will determine the minimum irrigation area of the fire center. The optimal choice of the calculated area for the water consumption when extinguishing a fire will optimize the parameters of the hydraulic distribution network, the choice of system elements, and calculate the effectiveness of the fire extinguishing system.

 

References

  1. John, R., Hall, Jr. (2013). U.S. Experience with Sprinklers and Other Automatic Fire Extinguishing Equipment. National Fire Protection Association, Quincy, MA. Retrieve from https://nfsa.org/wp-content/uploads/2019/07/US_experience_with_sprinklers_2009.pdf
  2. Ahrens, M. (2017). U.S. experience with sprinklers. Fire Analysis and Research Division, National Fire Protection Association. Retrieve from https://www.nfpa.org/-/media/files/news-and-research/fire-statistics-and-reports/suppression/ossprinklers.pdf
  3. John, R., Hall, Jr., Ahrens, M., Evarts, D. (2012). Fire Protection Research Foundation report: Sprinkler Impact on Fire Injury. Retrieve from https://www.nfpa.org/-/media/Files/Fire-Sprinkler-Initiative/Benefits-of-Home-Fire-Sprinklers/Sprinkler-Performance-and-Benefits/Impact-of-fire-sprinklers-on-firefighter-injuries.ashx
  4. ISO 6182-1:2014(en) Fire protection – Automatic sprinkler systems – Part 1: Requirements and test methods for sprinklers. Retrieve from https://www.iso.org/obp/ui/#iso:std:iso:6182:-1:ed-3:v1:en
  5. LPS 1039 Requirements and testing methods for automatic sprinklers. Issue 5.2. Retrieve from https://www.redbooklive.com/download/pdf/LPS1039.pdf
  6. Liu, H., Yuen, A. C. Y., Cordeiro, I., Han, Y., Chen, B. Y. T., Chan, Q. N., Kook, S., Yeoh, G. H. (2021). A novel stochastic approach to study water droplet/flame interaction of water mist systems. Numerical Heat Transfer. Part A: Applications, 79(8), 570–593. doi: 10.1080/10407782.2021.1872272
  7. Kagou, G., Kola, B., Mouangue, R. (2016). CFD studies of the propagation and extinction of flame in an under-ventilated and over-ventilated enclosure. Journal of Taibah University for Science, 10(3), 393–402. doi: 10.1016/j.jtusci.2015.04.010
  8. Nasif, M. S., Fekry, M., Ismail, F. B. (2016). CFD investigation on the effect of varying fire sprinkler orientation on sprinkler activation time. ARPN Journal of Engi-neering and Applied Sciences, 11(22), 12919–12922. Retrieve from http://www.arpnjournals.org/jeas/research_papers/rp_2016/jeas_1116_5323.pdf
  9. Arvidson, M. (2018). The Response Time of Different Sprinkler Glass Bulbs in a Residential Room Fire Scenario. Fire Technology, 54(5), 1265–1282. doi: 10.1007/s10694-018-0729-8
  10. Hopkin, C., Spearpoint, M., Bittern, A. Using experimental sprinkler actuation times to assess the performance of Fire Dynamics Simulator. Journal of Fire Sciences, 36 (4), 342–361. doi:10.1177/0734904118772306
  11. Lin, S.L., Chow, W.K., Woo, Y.K., Szeto, D.F., Su, C. H. (2019). Effect of heat collector plate on thermal sensitivity of sprinkler heads in large terminal Halls. Journal of Building Engineering, 25, 100787. doi: 10.1016/j.jobe.2019.100787
  12. Węgrzyński, W., Krajewski, G., Tofiło P., Król, A., Król, M. (2020). 3D mapping of the sprinkler activation time. Energies, 13(6), 1450. doi: 10.3390/en13061450
  13. Hopkin, C., Spearpoint, M. (2021). Numerical simulations of concealed resi-dential sprinkler head activation time in a standard thermal response room test. Journal of Fire Sciences, 42(1), 98–111. doi: 10.1177/0143624420953302
  14. Vondou, F. M., Abbe, C. V. N., Zaida, J. T., Mvogo, P. O., Mouangue, R. (2021). Experimental Study of the Effect of Confining on the Development of Fire in a Closed Compartment. Journal of Combustion, 2021, 6662830. doi:10.1155/2021/6662830
  15. BS EN 12845 (2015). Fixed Fire Fighting Systems – Automatic Sprinkler Systems – Design, Installation and Maintenance Retrieve from https://standards.globalspec.com/std/14212825/bs-en-12845
  16. Antonov, I., Velichkova, R., Antonov, S., Grozdanov, K. (2020). Mathemati-cal Modeling and Simulation of Development of the Fires in Confined Spaces. doi: 10.5772/intechopen.91274
  17. Koshmarov, Yu., Puzach, S., Andreev, V. et all. (2012). Forecasting of dan-gerous factors of fire indoors. Academy of State Fire Service of the Ministry of Emer-gency Situations, Moscow, Russia. Retrieve from https://www.twirpx.com/file/244202