Prevention of emergencies by monitoring the insulation condition of multi-core cables

 

Serhii Rudakov

National University of Civil Defenсe of Ukraine

http://orcid.org/0000-0001-8263-0476

 

Oksana Myrgorod

National University of Civil Defenсe of Ukraine

http://orcid.org/0000-0002-5989-3435

 

Ihor Hrytysyna

National University of Civil Defenсe of Ukraine

http://orcid.org/0000-0002-2581-1614

 

DOI: https://doi.org/10.52363/2524-0226-2021-33-20

 

Keywords: cable insulation, dielectric loss tangent, partial capacitance

 

Abstract

A method for measuring the partial capacities and the tangent of the dielectric loss angle of individual components of cable products that are in operation at energy facilities has been developed. This method is based on direct measurements of insulation components separately with subsequent assessment of the whole structure. This method makes it possible to assess in more detail the state of cable insulation, as cores, shields, metal sheaths are used as electrodes – to localize the probing electromagnetic field in certain parts of the cable: mainly in phase and solder insulation of power cables, in core insulation or in phase space control cables. Then, comparing the characteristics of the isolated areas of insulation with each other and with the basic products that have passed the accelerated resource tests, up to reaching the limit state – we make a reasonable conclusion about the current state of the cable product. However, in such measurements, the errors of partial capacitance measurements, and especially the tangent of the dielectric loss angle, can be large. The reason for this is the capacitive currents of the parasitic circuits discharged to the screen of the device. The paper proposes a method of reducing the mea-surement error, which limits the scope of the direct circuit only in cases where the capacity of the measured interval is much higher than the capacity of the parasitic circuits. The study on direct current is performed by devices with three terminals: two - measuring, the third - shielding - to remove excess current from the measuring circuit. The paper proposes such a scheme in the form of a triangle of capacitors, which allows for reliable measurements of the values of partial tanks, which compensates for the currents of the shunt circuits relative to the currents of the selected interval. The results of such control will allow to identify the areas of parameters that are most sensitive to the aging processes of cables, which, in turn, will prevent emergencies that could occur at energy facilities.

 

References

  1. Kouro, S., Malinowski, M., Gopakumar, K., Pou, J., Franquelo, L.G., Bin, Wu., Rodriguez, J., Pérez, M.A., Leon, J.I. (2010). Recent advances and industrial applica-tions of multilevel converters. IEEE Transactions on Industrial Electronics, 57 (8), 2553–2580.
  2. Krieger, E. M., Arnold, C. B. (2012). Effects of undercharge and internal loss on the rate dependence of battery charge storage effi-ciency. Journal of Power Sources, 210, 286–291.
  3. Chen, R. J., Zhang, Y., Wang, B. (2013). Numerical simulation study on the cement-based absorbing material. Advanced Materials Research, 853, 169–173.
  4. Saha, A., Ahmad, S., Soma, A. A., Chowdhury, M. Z., Hossain, A. A. (2017). Modelling and control of STATCOM to ensure stable power system operation. 4th In-ternational Conference on Advances in Electrical Engineering (ICAEE), 12–17.
  5. Pigini, A., Rizzi, G., Garbagnati, E., Porrino, A., Baldo, G., Pesavento, G. (1989). Performance of large air gaps under lightning overvoltages: experimental study and analysis of accuracy predetermination methods. IEEE Transactions on Power Delivery, 4(2), 1379–1392.
  6. Caldwell, R., Darveniza, M. (1973). Experimental and Analytical Studies of the Effect of Non-Standard Waveshapes on the Impulse Strength of External Insulation. IEEE Transactions on Power Apparatus and Systems, PAS-92, 4, 1420–1428.
  7. Jones, M., Satiawan, I. N. W., Bodo, N., Levi, E. (2012). A dual fivephase space-vector modulation algorithm based on the decomposition method. IEEE Transactions on Industry Applications, 48 (6), 2110–2120.
  8. Bezprozvannych, G. V., Kostiukov, I. A. (2020). Error of control of electrical insulation structures by dielectric absorption parameters according to the concept of uncertainty of measurements. Electrical engineering & electromechanics, 1, 47–51.
  9. Fesenko, H., Kliushnikov, I., Kharchenko, V., Rudakov, S., Odarushchenko, E. (2020). Routing an unmanned aerial vehicle during NPP monitoring in the presence of an automatic battery replacement aerial system. Proceedings of the 11th International Conference on Dependable Systems, Services and Technologies (DESSERT’2020), Kyiv, Ukraine, 34–39.
  10. Forthofer, J., Shannon, K., Butler, B. (2009). Simulating diurnally driven slope winds with WindNinja, in: Eighth Symposium on Fire and Forest Meteorology. Kalispell, MT, 156275.
  11. Batygin, Yu., Barbashova, M., Sabokar, O. (2018). Electromagnetic metal forming for advanced processing technologies. Springer International Publ, AG, 93.