Oleg Kulakov
National University of Civil Defenсe of Ukraine
https://orcid.org/0000-0001-5236-1949
Yuliia Mykhailovska
National University of Civil Defenсe of Ukraine
https://orcid.org/0000-0003-1090-5033
Albert Katunin
National University of Civil Defenсe of Ukraine
https://orcid.org/0000-0003-2171-4558
Oleksii Roianov
National University of Civil Defenсe of Ukraine
https://orcid.org/0000-0001-7631-1030
DOI: https://doi.org/10.52363/2524-0226-2023-37-8
Keywords: explosive zone, explosive environment, pump station, nomogram, room, light oil products
Аnnotation
Discrepancies between the international and national methods of classification of gas-vapor-air explosive zones (the method of the final edition of DSTU EN IEC 60079-10-1 and the method of NPAOP 40.1-1.32) were revealed using the example of the premises of pumping stations for pumping light petroleum products. When applying the international method, either an explosive zone of class 1 or an explosive zone of class 2 can be formed, or an explosive zone is not formed. The class of the zone depends on the mass rate of gasoline leakage and the ventilation rate (with a high mass rate of gasoline leakage and a low ventilation rate, a class 1 zone is formed; with an increase in the ventilation rate and the constant rate of gasoline leakage, either a class 2 zone is created or the conditions for its creation are absent). The explosive zone of class 2 acquires significant dimensions only in case of significant emergency leaks (in particular, it occurs at a distance of 5 m with a total mass leakage rate of 132,81 g per 1 kg of gasoline pumped). The explosive zone occupies the entire room only if its size exceeds the geometric dimensions of the room, taking into account the place of release of the hazardous substance. The time of existence of the explosive zone depends on the stationary background concentration of gasoline according to the logarithmic law. The frequency of air exchange in the room significantly affects the time of existence of the explosive zone. When applying the national method in the room, either an explosive zone of class 2 or no explosive zone can be formed. The criteria for the formation of an explosive zone by different methods differ significantly. The elimination of identified discrepancies is possible either by a complete transition to European technological regulations with the cancellation of the national method of calculation or by incorporating the international method of calculation into the existing national rules after their comprehensive technical examination.
References
- International Electrotechnical Commission (IEC). HIS Markit Standards Store. Available at: http://www.iec.ch
- National Fire Protection Association (NFPA). Available at: https://www.nfpa.org/
- British Standards Institution (BSI). Available at: https://www.com/
- Canadian Standards Association (CSA). Available at: https://www.scc.ca/
- Bozek, A. (2018). Application of IEC 60079-10-1 edition 2.0 for Hazardous Area Classification. IEEE Transactions on Industry Applications, 54, 1881–1889. doi: 1109/TIA.2017.2785258
- Bozek, A., Driscoll,T., Miller, J., Rowe, V., Lawrence, W. (2018). The Use of Combustible Gas Detection In Hazardous Locations: Additional Safety Precautions Around Flammable Gas Or Vapors. IEEE Industry Applications Magazine, 24, 64–74. doi: 1109/MIAS.2017.2740455
- Cole, М., Lawrence, W., Adams, D., Driscoll, T. (2017). The Canadian electrical code for hazardous locations has no class – But it does have significant changes. IEEE Transactions on Industry Applications, 53, 1635–1645. doi: 1109/TIA.2016.2622683
- Souza, A., Luiz, A., Neto, A., Araujo, A., Silva, H., Silva, S., Alves, J. (2019). A new correlation for hazardous area classification based on experiments and CFD predictions. Process Safety Progress, 38(1), 21–26. doi: 1002/prs.11974
- Alves, J., Neto, A., Araújo, A., Silva, H., Silva, S., Claudemi, A., Nascimento, C., Luiz, A. (2019). Overview and experimental verification of models to classify hazardous areas. Process Safety and Environmental Protection, 122, 102–117. doi: 10.1016/j.psep.2018.11.021
- Nascimento,, Luiz,A., Barros, P., Neto, A., Alves, J. (2021). A CFD-based empirical model for hazardous area extent prediction including wind effects. Journal of Loss Prevention in the Process Industries, 71, 104497. doi: 10.1016/j.jlp.2021.104497
- Kulakov, O. V., Katunin, A. M., Mykhailovska, Yu. V. (2022). Doslidzhennia klasiv i rozmiriv vybukhonebezpechnykh zon rezervuariv zi svitlymy naftoproduktamy. Problemy nadzvychainykh sytuatsii, 1(35), 133–146. doi: 10.52363/2524-0226-2022-35-10