Improving the installation of fire gasing with gelelating compounds

 

Kostiantyn Ostapov

National University of Civil Defenсe of Ukraine

https://orcid.org/0000-0002-1275-741X

 

Yuri Senchykhin

National University of Civil Defence of Ukraine

https://orcid.org/0000-0002-5983-2747

 

Volodymyr Syrovoi

National University of Civil Defenсe of Ukraine

https://orcid.org/0000-0001-6676-5565

 

Vadym Avetisian

National University of Civil Defenсe of Ukraine

https://orcid.org/0000-0002-5986-2794

 

DOI: https://doi.org/10.52363/2524-0226-2021-33-1

 

Keywords: gelling compounds, spray barrel, extinguishing system, plane-radial jet, remote fire extinguishing, exit section

 

Abstract

It is established that the organization of fire extinguishing with the use of gel-forming compounds is a promising direction to increase the efficiency of extinguishing, especially in multi-storey buildings and structures of various functional purposes. Given the shortcomings of existing technical solutions for the use of gel-forming compounds for effective fire extinguishing, the need to develop new structures (spray barrels) is justified. The proposed solutions should ensure, above all, the safety of the fire rescuer. New designs of spray barrels must have a distance of supply of gelling compounds to make work of the operator safe, as well as meet the general technical requirements for fire extinguishers. An autonomous installation of extinguishing with gelling compounds for remote fire extinguishing by plane-radial jets of components of gelling compounds has been developed. It is proposed to fix the spray barrels with a special device to guide them to the object that has to be extinguished with verification of the angles to the horizon, angles of deviation relative to the plane of aiming, the height and width of the symmetrical placement. In this manner, it allows more efficient feeding at a distance of up to 10 meters of the two components of the gelling compounds and prevents premature or delayed mixing. Full-scale samples of RS-10 spray barrels were designed and manufactured to supply flat-radial jets of gel-forming compounds at a distance of up to 10 m. The method of optimal planning of experiments was used to calculate rational values of geometric parameters of the initial cross-section of the RS-10 spray barrel. The problem of 4-factor (second-order) optimal planning of the experiment of the process of plane-radial jet supply by means of RS-10 spray barrels is formulated and carried out. The main design parameters of the spray barrel (cutout of the rigid plate sector and its thickness) are determined, which correspond to the area of rational geometric parameters. The obtained results can be used in the design of extinguishing systems with gelling compounds.

 

References

  1. Brushlinsky, N. N., Ahrens, M., Sokolov, S. S. (2020). World Fire Statistics // International Association of Fireand Rescue Services, 25, 67. Retrieve from https://www.ctif.org/sites/default/files/2020-11/CTIF_Report25_Persian-Edition-2020.pdf
  2. Norman, J. (2019). Fire Officers Handbook of Tactics 5th Edition // South Sheridan Road Tulsa. Oklahoma, 618. Retrieve from https://books.google.com.ua/books?id=BQRAvQEACAAJ&printsec=copyright&redir_esc=y#v=onepage&q&f=false
  3. Dubinin, D., Korytchenko, К., Lisnyak, А. (2018). Improving the installatio for fireex tinguishing with finely-dispersed water // Eastern-European Journal of Enterprise Technologies, 2(10 (92)), 38–43. doi: 10.15587/1729-4061.2018.127865
  4. Korytchenko, К., Sakun, О., Dubinin, D. (2018). Experimentalin vestigation of the fire-extinguishingsystemwith a gas-detonation charge fo rflui dacceleration // Eastern-European Journal of Enterprise Technologies, 3/5 (93), 47–54. doi: 10.15587/1729-4061.2018.134193
  5. Chow, W. K., Li, Y. F. (2013). A review on study index tinguishin groom fires by water mist // Journal of Applied Fire Science, 11(4), 367–403. doi: 10.2190/AF.23.1.d.
  6. Pospelov, B., Rybka, E., Meleshchenko, R. (2017). Results of experimental research into correlations between hazardous factors of ignition of materials in premises // Eastern-European Journal of Enterprise Technologies, 6, 10 (90), 50–56. doi: 10.15587/1729-4061.2017.117789
  7. Galla, S., Stefanicky, B., Majlingova, A. (2017). Experimental comparison of the fire extinguishing properties of the firesorb gel and water // 7th International Multidisciplinary Scientific GeoConference SGEM, 17(51), 439-446. doi: 10.5593/sgem2017/51/S20.058
  8. Stefanick, B., Poledňák, P., Rantúch, P. (2016). Assessment of wood fire protection effectiveness using blocking gel Firesorb // Production Management and Engineering Sciences, 4, 535–538. Retrieve from http://ndl.ethernet.edu.et/bitstream/123456789/12244/1/237.pdf#page=512
  9. Saveliev, D, Khrystych, O, Kirieiev, O. (2018). Binary fire-extinguishing systems with separate application as the most relevant systems of forest fire suppression // European Journal of Technical and Natural Science, 1, 31–36. Retrieve from http://repositsc.nuczu.edu.ua/bitstream/123456789/8354/1/EJT-1_2018-pages-1-2%2C31-36%2C42.pdf
  10. Gennady, N. Kuprin, Denis, S. (2017). Fast-Hardening Foam: Fire and Explosion Prevention at Facilities with Hazardous Chemicals // Journal of Materials Science Research, 6, 4, 56–61. doi:10.5539/jmsr.v6n4p56
  11. Dadashov, I., Kireev, A., Kirichenko, I. (2018). Simulation of the insulating properties of two-layer material. Functional Materials, 25, 4, 774–779. Retrieve from https://onlinelibrary.wiley.com/toc/16163028/2018/28/4
  12. Dadashov, I., Loboichenko, V., Kireev, A. (2018). Analysis of the ecological characteristics of environment friendly fire fighting chemicals used in extinguishing oil products. Pollution Research, 37, 1, 63–77. Retrieve from http://repositsc.nuczu.edu.ua/handle/123456789/6849
  13. Ostapov, K., Kirichenko, I., Senchykhyn, Y. (2019). Improvement of the installation with an extended barrel of cranked type used for fire extinguishing by gel-forming compositions. Eastern-European Journal of Enterprise Technologies, 4(10 (100)), 30–36. doi: 10.15587/1729-4061.2019.174592
  14. Ostapov, K. M., Senchihin, Yu. N., Syrovoy, V. V. (2017). Development of the installatio for the binary feed fgelling for mulations to extinguis hing facilities // Scienceand Education a New Dimension. Naturaland Technical Sciences, 132, 75–77. Retrieve from http: // repositsc.nuczu.edu.ua/handle/123456789/3891